Công ty TNHH công nghệ số Tân Thành

Bộ điều khiển nhiệt độ biến áp khô loại BWD-3K320B/C/D dry-type transformer computer temperature controller

  • Đăng ngày 29-12-2022 02:11:16 PM - 283 Lượt xem
  • Mã sản phẩm: S004297

  • Tình trạng sản phẩm:


     

    The wiring diagram on the back of the new BWD-3K320B is as follows:

    The physical picture of the old BWD-3K320B temperature controller is as follows: Jiangxi Qiyuan, Nanchang Xixia, Foshan Shunde Donghao and other manufacturers do not need to replace the sensor.

    The wiring diagram on the back of the old BWD-3K320B temperature controller (the old model uses a Pt100 probe. Many NTC thermistor probes on the market say it is a Pt100 probe. It has the same shape and is difficult to distinguish. It is recommended that buyers use a digital multimeter to adjust it to 200 ohms. The resistance value below 200 ohms is Pt100, and the resistance value of 500 ohms-100K is NTC thermistor, the cost is much lower than Pt100).

    Flip cover

    Product function introduction

    1. Detect and display the temperature of the three-phase wire wrap winding or only display the temperature of the highest temperature phase winding among the three-phase wire wrap windings. Each phase is displayed for about 8 seconds during the tour display.

    2. Fault sound and light alarm: When the sensor fails, the corresponding A, B, C phase indicator lights are on, and at the same time the fan is started, the machine emits a beep sound and the alarm contact is connected. The display shows X-HO or X-LO, where X indicates a faulty phase.

    3. Fan start and stop function: When the temperature of one phase in the three-phase wire package winding reaches the set fan start temperature value, the fan starts automatically, and the fan indicator lights up when the fan starts. When the temperature of none of the phases in the three-phase wire envelope group is higher than the set fan shutdown temperature value, the fan will automatically shut down.

    4. Over-temperature alarm function: When the temperature of one phase in the three-phase line covered wire group reaches the set over-temperature alarm temperature, the thermostat sends out sound and light alarms, and connects the alarm output terminal (usually between these two terminals is If it is disconnected, it will be connected when an alarm is issued) to provide a switch signal to send an audible and visual alarm to the remote control cabinet.

    5. Automatic tripping function: When one phase of the three sets of windings reaches the set tripping temperature value, the thermostat will connect the tripping output terminal (normally the two terminals are disconnected, and the two terminals are disconnected when tripping. will be connected) to provide a switch signal to the remote control cabinet to start the trip circuit. (There is a special delay of about 5S to prevent tripping due to accidental factors).

    6. Manually start and close the fan function: press the fan button, the fan starts, and press the fan button again, the fan turns off. If the manual fan is started without manually shutting down the fan, the fan will automatically shut down after about 15 minutes of starting.

    7. Fan timing detection function: In order to prevent the fan from being corroded and blocked due to long-term non-start, the fan timing detection function is specially provided. The timing start time can be set, and the range is 0-199 hours. When the set value is reached, the thermostat Automatically detect once to start the fan for about 2 minutes, and this function will be canceled when 000 is input.

    8. Control function self-test: It can simulate the input temperature signal to make the thermostat control accordingly.

    9. "Black box" function: it can record the temperature of the three-phase wire wrap winding when the thermostat is powered off, as well as the working status of the machine.

    10. All temperature settings can be directly set through the touch keys on the panel. In order to prevent setting by idlers, the thermostat has a password, which can only be set if the password is entered correctly, otherwise it can only be viewed but not set. See the table below for the setting temperature range:

    temperature T

    Factory setting temperature ℃

    Adjustable temperature range °C

    Fan off temperature T1

    80

    50-100

    Fan start temperature T2

    100

    60-110

    Over temperature alarm temperature T3

    130

    75-165

    High temperature trip temperature T4

    150

    90-170

    Note: When setting, T4>13>T2>T1+4 should be followed (4 is the minimum hysteresis value for fan start and stop)

         

     



    TÂN THÀNH CAM KẾT

    • Sản phẩm, hàng hóa chính hãng.
    • Giá cả cạnh tranh.
    • Dịch vụ chăm sóc khách hàng tận tâm.

    Thông Tin Công Ty

    Đã thông báo

     


    THÔNG TIN LIÊN HỆ:
    -------------------------------
    CÔNG TY TNHH THIẾT BỊ CÔNG NGHIỆP TTH
    Trụ sở: số 124 ngõ 79 Yên Hoà-Cầu giấy-HN
    Kinh doanh 1 : 0816.861.515
    Kinh doanh 2 : 0836.861.515
    Kinh doanh 3 : 0926.511.515
    Kinh doanh 4 : 0916.861.515
    Kinh doanh 5 : 0888.868.515
    Kinh doanh 6 : 0917.971.515
    Website: http://tanthanh-automation.com
    Website: http://thietbitudongtanthanh.com
    Website: http://diencongnghieptanthanh.com
    Email: tthkinhdoanh@gmail.com
    Email: tthkinhdoanh01@gmail.com

  • Kết nối với chúng tôi